Maximum auto-retransfer attempts, Figure 21 maximum auto-retransfer attempts screen – Liebert 610 User Manual

Page 39

Advertising
background image

Operation

33

Maximum Auto-Retransfer Attempts

When a UPS output overload condition exceeds a pre-programmed current-versus-time window, the

UPS automatically transfers the critical load to the bypass line. After the overload condition has been

corrected, the UPS attempts to automatically retransfer the critical load to the UPS output (unless

zero attempts is selected). The Maximum Auto-Retransfer Attempts limits the number of times

(0 to 5) that the UPS attempts to retransfer the load back to the UPS within a one hour time period.
If more than the selected number of overloads occurs during one hour, the critical load remains on the

bypass line and must be manually retransferred to the UPS system. Note that you should determine

the cause of any overload condition.

To change the Maximum Auto-Retransfer Attempts parameter, do the following:
1. From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto-

Retransfer Attempts.

2. Press the Select pad. The screen below will appear.
3. Press the Up pad to increase the value or the Down pad to decrease it.

Figure 21 Maximum auto-retransfer attempts screen

NOTE
Note that automatic retransfers are initiated only if the critical load was transferred to the

bypass line because of a system overload. If an automatic transfer to bypass occurred for any

other reason, an automatic retransfer will not be initiated. Refer to 3.5.3 - Automatic

Retransfers to UPS.

MAX AUTO-REXFER ATTEMPTS

UPPER LIMIT

5

LOWER INPUT

0

INCREASE

DECREASE

EXIT

UP :

DOWN :

SELECT :

VALUE

3

© 1989-2003

Advertising