3.3.4 Input Power Failure—Load on Battery

If the utility AC power source fails or is outside the acceptable range, the battery plant becomes the

power source for the UPS module inverters. The UPS system continues to supply power to the critical

load and also to the UPS controls.
You can use the Battery Time screen at the UPS modules to monitor the present battery voltage com-

pared to the shutdown value. The length of time the battery can sustain the load depends on the size

of the load and the size and condition of the battery plant. The battery plant is typically large enough

to supply a 100% rated load for 10-15 minutes.
Alarm messages that indicate battery status are Battery Discharge, Low Battery and Battery Shut-

down. The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings

screen. These limits were selected for your installation by Liebert Global Services during initial start-

up.
The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the

current in Amperes. Maximum battery discharge current ranges from 326 amps (for 150kVA) to 1619

amps (for 750kVA). Refer to the separate Installation Manual or drawings for specific data on your

system.

Figure 45 Input power fail—load on battery

OUTPUT

CB

Controls

Battery

Bypass CB

INPUT

CB

Static

Bypass

Switch

RIB

BFB

Critical

Load

AC Output

MBD

Static

Switch

Disconnects

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD