29

History Status

The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen.

Note that the values for output volts and amps are updated once each millisecond. Alarms are listed

in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a

computer information storage technique). The buffer stores the frames in a first in, first out (FIFO)

sequence. As a new frame enters the buffer the oldest one is released.
When a designated fault occurs (see list below), the buffer stores information for the next 24 frames

and then freezes (stops gathering information). At that time, the History Status screen contains

40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This

64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up

and Down pads to view the screens.

Figure 16 History status report screen

The alarm conditions that cause the History Status buffer to store and freeze data are:

Auto Transfer to Bypass
DC Cap Fuse Blown
DC Overvoltage Shutdown
Inverter Fault
Low Battery Shutdown
Output Overvoltage
Output Undervoltage
Overload Transfer
Overtemperature Time-out
Rectifier Fuse Blown
Reverse Power

For a complete list of all the alarm messages and corrective action to these faults, refer to Table 4.

The History Status buffer does not resume collecting new frames until the fault is cleared and the

Alarm Reset pad is pressed for more than 5 seconds (or until the screen clears).

NOTE
The Emergency Off and Hardware Shutdown alarms will also freeze the History Status buffer

with the Auto Transfer to Bypass alarm (if the load is on the UPS system when the alarm

condition occurs).

OUTPUT VOLTS

OUTPUT AMPS

OUTPUT FREQUENCY

OUTPUT VOLTS

OUTPUT AMPS

BATTERY VOLTS

OUTPUT VOLTS

OUPUT AMPS

BATTERY AMPS

INPUT VOLTS

INPUT AMPS

OUPUT VOLTS

OUTPUT AMPS

LOAD KVA

A

480

325

480

325

480

325

0

0

480

325

DC

390

-645

B

480

325

480

325

480

325

0

0

480

325

TIME

0:01

LOAD

270

C

480

325

480

325

480

325

0

0

480

325

HERTZ

60.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS MODULE-0 01/17/96 11:21:59 FRAME 100

ORDER - 000000 SITE ID - 00000 SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging Low Batt Warning