3.3.9 Maintenance Bypass

Maintenance Bypass switchgear allows you to totally isolate the UPS from all power sources, while

you maintain power to the critical load.
Your installation may have a two-breaker or three-breaker maintenance bypass or none at all. The

main difference between a two-breaker and three-breaker maintenance bypass is the location of the

Bypass Input Breaker (BIB).
Another option that may be present at your site is an alternate power source (generator) and an auto-

matic transfer switch (ATS).
Note that to totally isolate the UPS system from all power sources, the Main Input switchgear and

battery circuit breakers must also be opened.

Figure 50 Load on maintenance bypass (two breakers)

!

CAUTION

Instructions for operating the Maintenance Bypass circuit breakers are on the Maintenance

Bypass cabinet. Make sure you understand the proper sequence before operating any circuit

breaker. Operating a Maintenance Bypass circuit breaker out of sequence could cut off power

to the critical load.

Critical

Load

AC Output

RIB

MBD

MBFB

BIB

OUTPUT

CB

Controls

Battery

Bypass CB

INPUT

CB

Static

Bypass

Switch

Static

Switch

Disconnects

TWO BREAKER MAINTENANCE BYPASS SWITCHBOARD

CONTROL POWER

UPS MODULE

MAIN INPUT

SWITCHGEAR

Rectifier/

Charger

Inverter

MBB

MIB