6 alarm limit settings screen, Figure 29 alarm limit settings screen, Overload alarm – Liebert 610 User Manual

Page 46: Dc overvoltage, Battery discharging, Low battery, Battery shutdown (15 minutes), Alarm limit settings screen, Caution

Advertising
background image

Operation

40

3.2.6 Alarm Limit Settings Screen

Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad

and the Limit Settings screen is displayed.
The Alarm Limit Settings screen has Security Access to enable an authorized Liebert field-service

engineer to adjust the UPS system alarm limit settings

Figure 29 Alarm limit settings screen

Overload Alarm

This alarm setting initiates an alarm message on the display screen warning the operator that the

UPS system output current has exceeded the specified limit. This condition only activates an alarm.

The UPS does not shut down, but a separate control circuit will transfer the critical load to bypass if

the current and time of the overload condition exceeds system capability.

DC Overvoltage

This setting limits the maximum permitted level of the DC bus voltage. When this setting is exceeded,

an alarm indication appears on the module display screen, the UPS transfers the load to the bypass

line, and the input and battery circuit breakers trip open.

Battery Discharging

When the battery voltage on the DC bus falls below this limit for 5 seconds, a Battery Discharging

alarm message is displayed on the module screen. This means that the battery is discharging due to

an input voltage sag or interruption or a module output overload.

Low Battery

While the battery is discharging, this alarm warns the operator that the Battery Shutdown level is

approaching. This is generally set for a reserve time of approximately 5 minutes (typically 10 volts

above the 60-Minute Battery Shutdown voltage), based on full load operation.

Battery Shutdown (15 Minutes)

When the battery voltage decreases to this limit for five seconds during the first 15 minutes of the dis-

charge, the battery circuit breaker opens to prevent overdischarge. Note that the rated battery

reserve time at your site may be other than 15 minutes.

!

CAUTION

All alarm limit settings are application matched and factory-set. They should not be changed

casually. Contact Liebert Global Services for changing the alarm limit settings.

NOTE
The following battery alarm settings are factory-adjusted to the battery being utilized.

EXIT

SECURITY ACCESS

ALARM SETTINGS

CURSOR UP

CURSOR DOWN

CHOOSE

UP

:

DOWN

:

SELECT :

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

Overload Alarm ...............................
DC Over Voltage ...............................

Battery Discharging ...........................
Low Battery .......................................
Battery Shutdown (15 minutes) ......

Upper Point (60 minutes) ......

Battery Rating (100%) .....................

Battery Rating ...................................

104 %
600 VDC

480 VDC
437 VDC
384 VDC

427 VDC
500 KW 15 min

250 KW 45 min

Temperature Limit Setting ................ 28 C