Figure 4 series 610 ups operator control panel, Figure 4, Series 610 ups operator control panel – Liebert 610 User Manual

Page 25

Advertising
background image

Operation

19

Figure 4

Series 610 UPS operator control panel

Item

Description

Function

1

Display Screen

This screen displays all vital UPS information in one convenient location. All of the UPS

monitoring functions and conditions are indicated here.

2

Up

This touch-sensitive pad (button) is used to move the cursor up through various

selections present on the display screen. Note that all pads on this control panel have

touch-sensitive switches behind them.

3

Down

Similar to the Up pad, this pad is used to move the cursor down through the various

selections present on the display screen.

4

Select

After using the Up and Down pads to move the highlighted cursor to the desired menu

item on the display screen, push this pad to tell the microprocessor to go to the

highlighted selection.

5

Alarm Reset

This pad is used to clear all of the alarm conditions that are no longer present. However,

all active alarms remain in memory and on the applicable screens until they are

corrected.

6

Voltage Adjust

This push-to-turn knob permits adjustment of the UPS output voltage to meet load

requirements or to match the bypass voltage before transferring the load to or from

bypass.

7

UPS

This pad activates the circuits that connect the UPS inverter to the critical load (a

retransfer). When this pad is pushed (along with Control Enable), the UPS output circuit

breaker closes and the bypass circuit breaker opens.

8

Bypass

This pad activates the circuits that connect the bypass line to the critical load (a

transfer). When this button is pushed (along with Control Enable), the bypass circuit

breaker closes and the UPS output circuit breaker opens.

9

Battery Trip

This pad can be used (along with Control Enable) to trip the module battery disconnect

(MBD) circuit breaker open (disconnecting the battery from the UPS module).

10

Control Enable

This pad must be pressed simultaneously with the UPS, Bypass or Battery Trip pads to

activate them.

11

Horn Off

This pad is used to silence the alarm horn after it is activated. When this switch is

pressed, the alarm horn is silenced but the active and latched alarm messages remain

on the screen. The alarm messages still displayed stop flashing to indicate they have

been acknowledged.

12

Alarm Horn and Red LED

This electronic horn sounds to alert nearby personnel whenever a new alarm occurs. A

red LED (light emitting diode) is located in the middle of the alarm horn.

13

Emergency Module Off

During an emergency, pressing this guarded switch will transfer the load to bypass and

then shut down and disconnect the UPS inverter, rectifier and battery. The load will

remain on bypass power. (Refer also to 3.4.4 - Shutdown Procedures for additional

performance options.)