Battery shutdown (60 minutes), Battery rating (100%), Battery rating – Liebert 610 User Manual

Page 47: Temperature limit setting (optional)

Advertising
background image

Operation

41

Battery Shutdown (60 Minutes)

During extended outages or deep sags of more than 15 minutes, the shutdown voltage limit will ramp

up gradually to this 60-minute limit to prevent lengthy discharge and possible battery damage. The

battery circuit breaker opens when the battery voltage and the shutdown limit are equal for five sec-

onds. See the Battery Time screen for more information. Also refer to the battery manufacturer’s

manual, available on the manufacturer’s Web site.

Battery Rating (100%)

This setting is the full load discharge rating of the battery in kilowatts for the rated backup period. A

typical rating might be 500 kW for 15 minutes.

Battery Rating

This setting is a battery discharge rating in kilowatts under partial load for an extended period, typi-

cally 40 to 60 minutes. The UPS uses the two battery shutdown voltage settings and the two battery

discharge ratings in computing rated and calculated time remaining during a discharge event.

Temperature Limit Setting (Optional)

This setting is visible when the optional battery-temperature-compensated charging board is

installed. This setting determines the battery temperature that triggers the Battery Overtemp alarm.

The alarm becomes active when the temperature setting is exceeded for more than one minute.

NOTE
The Low Battery alarm setting is designed to be useful at full load battery discharge rates. It is

typically set for 10 volts above the 60-minute Battery Shutdown voltage, to provide some

measure of warning under all circumstances. If the discharge period extends past 15 minutes

(i.e., the load on the UPS is less than full capacity), the Battery Shutdown voltage setting is

gradually and automatically increased to protect the batteries from deep discharge. The Low

Battery alarm setting is not automatically increased and will give proportionately less

warning for longer discharge periods. Instead, the operator should consult the Battery Time

screen or Present Status screen to see the calculated time remaining based on actual usage

during the discharge period.

Advertising