12 battery equalize screen, Figure 39 battery equalize screen, Caution – Liebert 610 User Manual

Page 54

Advertising
background image

Operation

48

3.2.12 Battery Equalize Screen

Go to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select

pad and the Battery Equalize screen is displayed.

Figure 39 Battery equalize screen

The Battery Equalize screen enables the operator to adjust the battery equalize time. It is also used to

choose between auto and manual battery equalize recharging modes.
When the input utility power is interrupted, the battery supplies DC power to the inverter so there is

no interruption of power to the critical load. When the AC input power is restored, the battery equal-

ize recharging circuit can be activated automatically or manually to increase the rectifier/charger out-

put voltage to recharge the battery. The battery equalize circuit may be manually activated at any

time during normal float (constant) voltage operation. The equalizing time can be adjusted from

0 to 72 hours.

EQUALIZE TIME PERIOD. This selection permits the operator to adjust the battery equalize time

in one-hour increments from 0 to 72. The battery equalize time must be greater than zero for the bat-

tery to begin recharging in both the AUTO and the MANUAL modes. This period is set by use of the

Up/Down pads and Select pad.
When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME

PERIOD (hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAINING

(hrs). After the equalize recharge time has expired, the indication returns to the preset equalize time.
STOP EQUALIZE CHARGE. This selection lets the operator halt the equalizing charge to the bat-

tery at any time, whether the circuit was activated automatically or manually.
MANUAL MODE. This mode enables the operator to manually initiate a battery equalize charge to

raise the DC bus voltage to correct a non-uniformity in the individual cell voltages or specific gravity

readings.
AUTO MODE. When the battery recharge control logic is in the AUTO MODE, the UPS battery

charger attempts the equalization process only if the EQUALIZE TIME PERIOD is greater than zero,

the battery voltage has been at or below the Battery Discharging alarm limit for longer than 30 sec-

onds, and the battery breaker (MBD) is closed.

!

CAUTION

Do not use the Battery Equalize mode if you have valve-regulated, lead-acid batteries. Refer

to your battery manufacturer’s manual, available on the manufacturer’s Web site.

EXIT

SECURITY ACCESS

BATTERY EQUALIZE RECHARGING

0

NO

NO

YES

NO

EQUALIZE TIME PERIOD (HRS.)

STOP EQUALIZE CHARGE

MANUAL MODE

AUTO MODE

MANUAL / RESET TO AUTO MODE

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :