Figure 3 operator controls, typical system, Figure 3, Operator controls, typical system – Liebert 610 User Manual

Page 24

Advertising
background image

Operation

18

Figure 3

Operator controls, typical system

Refer also to Figure 2 for a typical system one-line diagram.

Item

Description

Function

1

Input Circuit Breaker

(CB1)

This manually operated circuit breaker provides power to the UPS module rectifier. It is

located in the transformer cabinet of certain 500kVA and all 625, 750 and 1000kVA modules.

2

Control Disconnect

(behind door)

These two fuses provide power to the controls. They are normally closed (ON). Turn Control

Power OFF (by opening the two fuseholders) only for maintenance procedures.

3

Operator Control Panel

Refer to Figure 4 for controls available on this panel.

4

Bypass Reset Switch

(behind door above

breakers)

Press this button to reset the transfer relays during start-up after an Emergency Power Off

shutdown. You must press this button before resetting the Close B.P. jumper (Item 5).

5

Close B.P. Switch

(behind door, on main

logic board)

Press switch to close the bypass circuit breaker during a start-up procedure, if it remains

open after a shutdown procedure. Refer also to 3.4.1 - Start-Up Procedure and Bypass

Reset Switch (Item 4 above). Note that the static switch disconnects must be open for this

jumper to close the bypass breaker.

6

Interlock Button (on rear

of Control Panel)

Press this button to make authorized changes to any site parameter protected by the Security

Access function. These include the time, date, auto-dial phone number and other site

parameters.

7

Bypass Circuit Breaker

(behind control panel)

This motorized circuit breaker connects the critical load to the bypass line.

8

Output Circuit Breaker

(behind control panel)

This motorized circuit breaker connects the critical load to the UPS inverter output.

100kVA-

500kVA

3

1

7

8

6

4

2

5

1000kVA