Figure 5 illustrates the primary screens that you can access through the Operator Interface Display

System. The liquid crystal display (LCD) screen provides a full 80 characters by 25 lines of informa-

tion for easy readability. The following sections describe what these screens display and how and

when to use them.
System status information is available on the display screen and at local and remote terminals, pro-

vided Control Power is ON, even when the UPS module is not operating.
The screen will automatically display the Monitor/Mimic during normal operation. The System con-

figuration screen will be displayed during start-up and whenever a system reset is required.
If a module display screen is blank, either power is not available, the Rectifier Input (RIB) circuit

breaker (external to the UPS module) is open or the Control Power switch is OFF. If power is avail-

able and a display is blank, contact Liebert Global Services (1-800-LIEBERT). Note that status infor-

mation may be available at local and remote terminals. Use control touch pads to manually transfer

the critical load to the bypass line if the display goes blank while load is on UPS (a very unlikely

event).

3.2.1 Master Menu Screen

The Master Menu contains the primary menu selections that monitor and control the operation of the

UPS.

Figure 6

Master menu screen

From any primary screen (accessed directly from the Master Menu), pushing the Select pad once will

return you to the Master Menu. From any secondary screen, pushing the Select pad twice will return

you to the Master Menu.
Please note that some screens have multiple pages. However, in each case, instructions appear for

accessing other pages.

Monitor/Mimic Display—This graphic mimics the power flow through the UPS. Input voltage

and current readings, battery status, UPS ratings, load readings, circuit breaker indications, sys-

tem status and alarm messages are all displayed on this screen.

Walk-In Display—This is a bar graph that shows DC bus voltage, input currents and UPS mod-

ule output voltage (all in percent of nominal). This screen typically is utilized during start-up pro-

cedures.

Status Reports—This display consists of four submenu selections: present status, event history,

history status and system status. These screens display data on the system’s present and past

performance. They also display information about any faults that have occurred in the system.

Total operating hours (for controls) are displayed here.

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

WALK-IN DISPLAY
STATUS REPORTS
SYSTEM CONFIGURATION
LIMIT SETTINGS
LOAD TRANSFER PROCEDURES

START-UP PROCEDURES
SHUTDOWN PROCEDURES
BATTERY TIME
METER CALIBRATION
BATTERY EQUALIZE
CUSTOMER ALARM DEFINITIONS

Down

MONITOR/MIMIC DISPLAY

MASTER MENU

Select

Alarm
Reset

Up

BATTERY TEMP COMP. CHARGING