59

3.3.2 OK to Transfer

The OK to Transfer status message will be displayed when the bypass line and UPS output power are

both available, their voltage, frequency and phase synchronization are matched within specifications,

and the Static Switch Disconnects are closed (ON). An alarm message may be displayed to indicate

Load On Bypass (Figure 42). If no alarm is displayed, the operating status is Load On UPS

(Figure 43).
When the OK to Transfer message is displayed, you can perform a manual transfer of the load from

the UPS system to bypass or a manual retransfer of the load from bypass to the UPS system.
Use the Load Transfer Procedures screen when performing a manual transfer. Refer to 3.4.2 - Load

Transfer Procedures.

Figure 42 Load on bypass (UPS available)

The UPS system control logic will initiate an automatic transfer to bypass if an overload condition

exceeds the system current versus time window or if a UPS fault is detected. An automatic retransfer

to the UPS system may be initiated when recovering from system overloads lasting less than five min-

utes. Refer to 3.5 - Automatic Operations.

OUTPUT

CB

Rectifier/

Charger

Controls

Battery

Bypass CB

INPUT

CB

Static

Bypass

Switch

Inverter

RIB

BFB

Critical

Load

AC Output

MBD

Static

Switch

Disconnects

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

CONTROL POWER

UPS MODULE

MAIN INPUT

SWITCHGEAR

BIB

MBB

MIB