Operation

65

3.3.7 Remote Emergency Power Off

The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.
The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS

system. It will normally be in the same room as the critical load equipment. This mode can also be ini-

tiated by an automatic contact closure in the same external circuit as the manually operated switch.
When you operate the Remote Emergency Power Off switch, all UPS circuit breakers are opened,

including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,

the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS

controls.
Refer to 3.4.4 - Shutdown Procedures.