4 shutdown procedures, Module shutdown procedure, Figure 55 shutdown procedures screen – Liebert 610 User Manual

Page 82: Figure 56 shutdown procedures screen, continued, Shutdown procedures, 4 shutdown procedures module shutdown procedure, Step 1 (shutdown procedures), Step 2 (shutdown procedures)

Advertising
background image

Operation

76

3.4.4 Shutdown Procedures

Module Shutdown Procedure

Perform a Module Shutdown Procedure when you want to remove power from a UPS module when

required for maintenance.
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARNINGS

in 4.0 - Maintenance.
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.

STEP 1 (Shutdown Procedures)

From the module Master Menu, select the Shutdown Procedures screen. Note that this is a two-page

screen.
If the UPS module is supplying power to the load (Load On UPS), select the Load Transfer Procedures

screen and perform a manual transfer to the bypass line (Load on Bypass), see 3.4.2 - Load Transfer

Procedures. This will open the UPS module output motorized circuit breaker (Figure 3).

Figure 55 Shutdown procedures screen

Figure 56 Shutdown procedures screen, continued

STEP 2 (Shutdown Procedures)

Open the module battery disconnect (MBD) circuit breaker by simultaneously pressing the Battery

Trip and Control Enable pads (Figure 4).

SHUTDOWN PROCEDURES

NEXT PAGE

MASTER MENU

1.

If load is not already being supplied by the bypass line, select the

"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer

the load to bypass.

2.

Open the battery breaker by simultaneously pressing the BATTERY TRIP and

CONTROL ENABLE pushbuttons.

3.

Manually open the input breaker by moving the handle to the OFF position.

4.

Verify breaker status on the "MONITOR / MIMIC" screen.

5.

Press the ALARM RESET button to clear alarms which are no longer active.

DOWN :

SELECT :

FIRST PAGE

MASTER MENU

6.

If necessary for maintenance purposes, open the static switch disconnects

and/or control power switch (fuse disconnect on some models) to the OFF

position.

7.

Wait a minimum of two (2) minutes before attempting any other action.

UP :

SELECT :

SHUTDOWN PROCEDURES (Cont'd)