3.3.8 Module Shutdown

Perform a Module Shutdown procedure when you must disconnect the UPS system components from

all power sources when required for maintenance procedures.
Use the Shutdown Procedures screen when performing a manual System Shutdown.
Refer to 3.4.4 - Shutdown Procedures.
Refer to 3.3.9 - Maintenance Bypass.
Before performing any maintenance on your Liebert Series 610 UPS System, observe ALL of the

WARNINGS in 4.0 - Maintenance.

Figure 49 Module shutdown

!

WARNING

Lethal voltages are present within this system even when it is not on or when power is not

being supplied. Observe all cautions and warnings in this manual. Failure to do so could

result in serious injury or death. Do not work on or operate this equipment unless you are

fully qualified to do so! Never work alone.

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

OUTPUT

CB

Rectifier/

Charger

Controls

Battery

Bypass CB

INPUT

CB

Static

Bypass

Switch

CONTROL POWER

UPS MODULE

Inverter

RIB

BFB

MAIN INPUT

SWITCHGEAR

Critical

Load

AC Output

MBD

Static

Switch

Disconnects

BIB

MBB

MIB