3 battery charging circuit, Operation after discharge, Operation after end-of-discharge – Liebert 610 User Manual

Page 18: Battery disconnect, Battery charge current limiting, Battery equalize charge circuit, Battery charging circuit

Advertising
background image

Theory of Operation

12

2.2.3 Battery Charging Circuit

The UPS module charging circuit is capable of recharging the battery plant to 95% of full capacity

within 10 times the discharge time. Recharging the last 5% takes longer because of characteristics

inherent in the battery. DC ripple voltage is limited to 0.5% RMS to preserve battery life during long-

term float charging while the UPS system is operating on utility source power.

Operation After Discharge

When commercial power is interrupted, the battery continues to supply DC power to the inverter

without interruption to the critical load. If the AC source power is restored before the battery has

fully discharged, the rectifier automatically restarts and resumes carrying the inverter and battery

recharge load requirements.

Operation After End-of-Discharge

The battery time screen displayed on the control panel enables you to estimate when battery shut-

down will occur. If the battery plant discharges to the shutdown point during an outage, the UPS

automatically disconnects the load, the AC input and the battery. After AC input power is restored,

the rectifier can be manually restarted by the user.

Battery Disconnect

The module battery disconnect (MBD) circuit breaker is used to isolate the UPS module from the bat-

tery during maintenance and to automatically disconnect the battery from the inverter at the end of

battery discharge. The MBD circuit breaker can be opened or tripped automatically, from the control

panel or manually. It must be closed manually.

Battery Charge Current Limiting

The battery recharge current, after a battery discharge, is adjustable to between 1 and 25% of the full

load maximum discharge current. An external dry contact closure (field supplied) activates a reduced

second level of the battery charge current limiting circuit for use with a back-up generator. These two

levels of control regulate the amount of current that flows from the power source to the battery while

the battery is recharging.
The battery charge current limit is factory-set at 10% for normal operation and at 1% for alternate

power source recharge operation.

Battery Equalize Charge Circuit

The battery equalize charge feature can be manually initiated or it can be programmed to operate

automatically. Either can be selected from the battery equalize screen displayed on the control panel.
The automatic battery equalizing charge circuit increases the rectifier/charger output voltage to

charge the battery any time there is a power outage of 30 seconds or longer. The equalizing voltage is

slightly higher than the float voltage. Equalize charging is primarily used in flooded battery systems

to boost individual cells that are at a low state of charge, per the battery manufacturer's specification

and recommendations.

NOTE
Do not use equalize charging with valve-regulated lead-acid batteries.
Consult the battery manufacturer’s manual, available on the manufacturer’s Web site, for

specific information about equalize charging.