7 load transfer procedures screen, Figure 30 load transfer procedure screen, Load transfer procedures screen – Liebert 610 User Manual

Page 48: Caution

Advertising
background image

Operation

42

3.2.7 Load Transfer Procedures Screen

Go to the Master Menu and move the highlighted cursor to LOAD TRANSFER PROCEDURES. Press

the Select pad and the Load Transfer Procedures screen is displayed.

Figure 30 Load transfer procedure screen

The Load Transfer Procedures screen contains instructions to transfer the critical load between the

UPS system and the bypass line. Comparisons of the UPS and bypass voltage, frequency and phase

synchronization are displayed along with transfer status messages. The metered parameter values on

the Load Transfer Procedures screen are updated at half-second intervals.
Refer to 3.3 - Modes of Operation and 3.4.2 - Load Transfer Procedures for more details.
Item 1 - Voltage Comparisons: This chart shows the UPS and bypass voltage and frequency com-

parisons between each of the three phases. If the UPS and bypass voltages are not within specified

tolerances, a manual transfer is not permitted and TRANSFER PROHIBIT is highlighted.
The Voltage Adjust knob (push-to-turn), located on the Operator Control Panel (Figure 4), is used

to match the UPS output voltage to the bypass voltage. When the UPS and bypass voltages match

within the specific tolerance, a manual transfer is possible and OK TO TRANSFER is highlighted.

Item 2 - Synchronization: This display shows the phase synchronization between the UPS output

and bypass power. If the phase displacement is outside of the tolerance, a manual transfer is not per-

mitted and TRANSFER PROHIBIT is highlighted.
During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.
Item 3 - Status Messages: Three messages are constantly displayed here. Only the active message

is highlighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be per-

formed and automatic retransfers will not be initiated.
Item 4 - Manual Transfer Instructions: These instructions assist the operator in transferring the

critical load between the UPS system and the bypass line.
If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control

Enable buttons to retransfer the load from the bypass line to the UPS system.

!

CAUTION

The UPS output voltage responds very slowly to inputs from the Voltage Adjust knob. Make

small adjustments and wait several seconds each time for voltage to stabilize before

continuing.

TRANSFER PROHIBIT

UPS LEAD = 2 Deg

UPS -

BYPASS -

480

480

480

481

B-C

A-B

VOLTAGE COMPARISON

SELECT : MASTER MENU

OK TO TRANSFER

+30

ON UPS

60.0 Hz

479

C-A

FREQUENCY

MANUAL

TRANSFER INSTRUCTIONS

1.

Adjust the UPS voltage until it equals the

bypass voltage with the VOLTAGE ADJUST pot.

2. If the OK TO TRANSFER message is highlighted,

simultaneously press the BYPASS and CONTROL ENABLE

buttons.

3. Verify that the transfer was successful by checking the

breaker status on the "MONITOR/MIMIC" screen.

4. Press the ALARM RESET button to clear alarms which

are no longer active

SYNCHRONIZATION

60.0 Hz

0

-30

480

1

2

4

3