3.2.13 Alarm and Status Messages

Status Messages

The status messages indicate whether the static bypass switch is connected or disconnected. The sta-

tus messages also advise the operator when a transfer or retransfer between the UPS and bypass line

is permitted, based on matching voltage, frequency and phase.
The following status messages may appear in the system status area.
1. Static Switch Connected. The static switch is connected (the disconnect switches are closed—

ON) and is ready to provide a current path from the bypass input to the load.

2. Static Switch Disconnected. The static switch is disconnected (the disconnect switches are

open—OFF) for maintenance procedures.

3. OK to Transfer. The UPS system voltage, frequency and phase match the bypass line. This

means that a transfer between the bypass line and the UPS is permitted.

4. Not OK to Transfer. Either the UPS or bypass voltage, frequency or phase is not within the

specified limits or the static bypass switch is not available. Therefore, manually initiated transfer

between the bypass line and the UPS is not permitted. Emergency or overload transfer to bypass

may still be available provided the “Static Switch Unable” alarm is not indicating.

5. Time to Overload Transfer. During an overload condition, the time remaining before transfer

(in seconds) is displayed at the bottom of the load block.

Figure 40 Alarm and status message screen

STATUS

MESSAGES

VOLTS 480
AMPS 645 DISCHARG

UPS RATINGS

A-B B-C C-A

480V 480V 480V

60.0 Hz

AP658-64

RATED 500 KVA

OUTPUT VOLTAGE

LOAD

A B C

270 KVA / 217 KW

325A 325A 325A

Time To Overload
Transfer: XXXX SEC

UPS INPUT PWR

BYPASS INPUT

A-B B-C C-A

0V 0V 0V

0 Hz

480V 480V 480V

0A 0A 0A

A-B B-C C-A

Byp Not Avail
Input Fail
Batt Discharging

ALARM

MESSAGES

BATTERY

Not OK to Transfer
Static Switch Connected