Important safety instructions, Mportant, Afety – Liebert 610 User Manual

Page 7: Nstructions, Warning, Save these instructions

Advertising
background image

1

I

MPORTANT

S

AFETY

I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation and mainte-

nance of your Series 610 UPS and batteries.

!

WARNING

Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to

personnel. Refer to separate installation manual for equipment handling information and

installation procedures.
Follow all battery safety precautions in 4.0 - Maintenance when installing, charging or

servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can

be explosive and sulfuric acid can cause severe burns.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or

others approved for use in electrical fire fighting.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages. With

input power off and the battery disconnected, high voltage at filter capacitors and power

circuits should be discharged within 30 seconds. However, if a power circuit failure has

occurred, you should assume that high voltage may still exist after shutdown. Check with a

voltmeter before making contact.
AC voltage will remain on the system bypass, the UPS output terminals and the static bypass

switch, unless associated external circuit breakers are opened.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the UPS system is under power, both the operator and any test equipment must be

isolated from direct contact with earth ground and the UPS chassis frame by using rubber

mats.
Some components within the cabinets are not connected to chassis ground. Any contact

between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the

test instrument exterior does not make contact either physically or electrically with earth

ground.

Advertising