3.2.9 Shutdown Procedures Screen

Go to the Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad

and the Shutdown Procedures screen is displayed.
This two-page screen contains the steps you must follow to perform a controlled shutdown of the UPS

system. The instructions are listed so you can review them before performing the controlled shutdown.
To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line.

Then open the battery circuit breaker and manually open the UPS input circuit breaker. The Control

Power may be turned off (by pulling open the two fuseholders labeled Control Disconnect) if required

for maintenance purposes.
Refer to 3.4.4 - Shutdown Procedures for more details, including module shutdowns for service and

emergency shutdowns.

Figure 33 Shutdown procedures screen

Figure 34 Shutdown procedures screen, continued

3.2.10 Battery Time Screen

At the Master Menu, move the highlighted cursor to BATTERY TIME. Press the Select pad and the

Battery Time screen is displayed.
When AC power is not available to the UPS module, the UPS inverter uses DC power from the battery

to supply the critical load. This screen helps the operator assess his power resources to determine if

and when the critical load shutdown procedures need to be started.
The Battery Time screen is a line graph that tracks the present battery voltage versus the elapsed

time that the battery has been discharging (Figure 35). As the battery voltage decreases, the line

representing it moves closer to intersecting the line that represents the battery shutdown voltage.

When the battery starts to discharge, the screen displays a 15-minute graph. If the battery has been

providing power for more than 15 minutes, the screen displays a 30-minute graph. If battery power is

still available after 30 minutes, a 60-minute graph is displayed (Figure 36).

SHUTDOWN PROCEDURES

NEXT PAGE

MASTER MENU

1.

If load is not already being supplied by the bypass line, select the

"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer

the load to bypass.

2.

Open the battery breaker by simultaneously pressing the BATTERY TRIP and

CONTROL ENABLE pushbuttons.

3.

Manually open the input breaker by moving the handle to the OFF position.

4.

Verify breaker status on the "MONITOR / MIMIC" screen.

5.

Press the ALARM RESET button to clear alarms which are no longer active.

DOWN :

SELECT :

© 1989-2003

FIRST PAGE

MASTER MENU

6.

If necessary for maintenance purposes, open the static switch disconnects

and/or control power switch (fuse disconnect on some models) to the OFF

position.

7.

Wait a minimum of two (2) minutes before attempting any other action.