4.1.4 Connecting the Bus Line

Connect bus wire NET A to terminal 79 and NET B to 80 of the terminal connector.

Terminal

Connection

79

NET A*

80

NET B*

61

Drain**

NB!
*Note:
For free topology wiring the option is insensitive to the polarity of the bus-terminals.

NB!
**Note:
Term. 61 (Drain) offers a RC-junction to ground and should not be used for grounding of shielded cable. Ground the shielded cable at the de-coupling
plate by removing cable insulation at contact point.

4.1.5 Maximum Cable Lengths

Network topology

Maximum cable length

Free topology without repeater

500 m

Free topology with one repeater

1000 m

Free topology maximum device-to-device

500 m

Bus topology single terminated

500 m

Bus topology double terminated without repeater

2700 m

Bus topology double terminated with one repeater

5400 m

Bus topology maximum stub length

3 m

Use of the same cable type throughout the entire network is recommended in order to avoid impedance mismatch.

4.1.6 System Specifications

Up to 64 FT-X1/FTT-10 transceivers, are allowed per network segment.

NB!
Note:
The Free Topology LonWorks runs at 78 Kbps only.