Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 25

Advertising
background image

DC Link Voltage [V]

Variable
name:

SNVT
type:

Value:

nvoDCVoltage

SNVT_volt

Min.

Max.

Resolution:

0 V

10,000 V

0.1 V

This variable contains the measured Dc-link voltage. The value is filtered and therefore may be delayed with up to 1.3 seconds before a voltage change is reflected
in the output variable.

Motor Thermal [%]

Variable
name:

SNVT
type:

Value:

nvoTempMrt

SNVT_lev_cont

Min.

Max.

Resolution:

0 %

100 %

0.5 %

This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.

Inverter Thermal [%]

Variable
name:

SNVT
type:

Value:

nvoTempInvrtr

SNVT_lev_cont

Min.

Max.

Resolution:

0 %

100 %

0.5 %

This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.

Closed Loop Feedback

Variable
name:

SNVT
type:

Value:

nvoFeedback

SNVT_count_inc_f

Min.

Max.

Resolution:

0 %

100 %

0.5 %

This variable contains the summerized amount of network feedback in closed loop mode.

Fanbelt broken

Variable
name:

SNVT
type:

State:

Value:

Command:

nvoBrokenbelt

SNVT_switch

0 (False)

Any

Fanbelt not broken

1

(True)

Any

Fanbelt

broken

This variable indicates whether the fanbelt is intact or broken (indicated by bit 8 in Warning Word 2).

AF-600 FP LonWorks