8 Parameters

8.1 Parameter List

8.1.1 Parameter List

Par. No.

Parameter name:

Default value:

Range:

Conversion

type:

Data type:

O-01

Control Site

Dig. and control word [0]

[0 - 2]

-

5

O-02

Control Word Source

Drive Port [1]

[0 - 4]

-

5

O-03

Control Word Timeout Time

600 s

0.1 - 18000

1

7

O-04

Control Word Timeout Function

Off [0]

[0 - 10]

-

5

O-05

End-of-timeout Function

Hold set-up [0]

[0 - 1]

-

5

O-06

Reset Control Word Timeout

Do not reset [0]

[0 - 1]

-

5

O-07

Diagnosis Trigger

Disable [0]

[0 - 3]

-

5

O-10

Control Word Profile

Drive profile [0]

[0 - x]

-

5

O-50

Coasting Select

Logic OR [3]

[0 - 3]

-

5

O-52

DC Brake Select

Logic OR [3]

[0 - 3]

-

5

O-53

Start Select

Logic OR [3]

[0 - 3]

-

5

O-54

Reversing Select

Logic OR [3]

[0 - 3]

-

5

O-55

Set-up Select

Logic OR [3]

[0 - 3]

-

5

O-56

Preset Reference Select

Logic OR [3]

[0 - 3]

-

5

LN-00

Neuron ID

00 00 00 00 00 00

-

-

10

LN-10

Drive Profile

VSD 6010 [0]

-

-

5

LN-15

Lon Warning Word

0

-

-

6

LN-18

LonWorks Revision

[0, 10]

-

-

9

LN-21

Store Data Values

Off [0]

[0 - 1]

-

5

8.2 Parameter Group O-##

O-01 Control Site

Option:

Function:

The setting in this parameter overrides the settings in par.O-50 Coasting Select to par.O-56 Preset Refer-
ence Select
.

[0] *

Digital and ctrl.word

Control by using both digital input and control word.

[1]

Digital only

Control by using digital inputs only.

[2]

Controlword only

Control by using control word only.

O-02 Control Word Source

Option:

Function:

Select the source of the control word: one of two serial interfaces or four installed options. During initial
power-up, the drive automatically sets this parameter to Option A [3] if it detects a valid network option
installed in slot A. If the option is removed, the drive detects a change in the configuration, sets
par.O-02 Control Word Source back to default setting Drive Port, and the drive then trips. If an option is
installed after initial power-up, the setting of par.O-02 Control Word Source will not change but the drive
will trip and display: Alarm 67 Option Changed.

[0]

None

[1]

Drive Port

[2]

USB Port

[3] *

Option A

AF-600 FP LonWorks

47

8