Af-600 fp lonworks, 1 drive speed, 2 output current – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 32: 3 output voltage, 4 output power, 5 running hours

Advertising
background image

5.5 Network Variable Description - VSD Profile - Output

5.5.1 Drive Speed

Variable
name:

SNVT
type:

Value:

nvoDrvSpeed

SNVT_lev_percent

Min:

Max:

Resolution:

-163.840 %

+163.830 %

0.005 %

This variable contains the frequency converter speed as a percentage of the nominal speed.

5.5.2 Output Current

Variable
name:

SNVT
type:

Value:

nvoDrvCurnt

SNVT_amp

Min:

Max:

Resolution:

0 A

3,276.6 A

0.1 A

This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.

5.5.3 Output Voltage

Variable
name:

SNVT
type:

Value:

nvoDrvVolt

SNVT_volt

Min:

Max:

Resolution:

0 V

3,276.6 V

0.1 V

This variable contains the frequency converter output voltage.

5.5.4 Output Power

Variable
name:

SNVT
type:

Value:

nvoDrvPwr

SNVT_power_kilo

Min:

Max:

Resolution:

0 kW

6,554.4 kW

0.1 kW

This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.

5.5.5 Running Hours

Variable
name:

SNVT
type:

Value:

nvoDrvRunHours

SNVT_time_hour

Min:

Max:

Resolution:

0

hr

65,534

hr

1

hr

This variable contains the total running hours of the motor.

AF-600 FP LonWorks

31

5