5.6 Network Variable Description - VSD Profile - Configuration

5.6.1 Max Motor Speed [%]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciMaxSpeed

SNVT_lev_percent

100 %

0 %

163.830 %

This variable configures the maximum motor speed in % and associates it with par. F-17 Motor Speed High Limit [RPM] (par. F-15 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the How to Control the AF-600 FP section. If a value higher than 163.830% is requested, use the parameter
access command.

5.6.2 Min Motor Speed [%]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciMinSpeed

SNVT_lev_percent

0 %

0 %

163.830 %

This variable configures the minimum motor speed in % and associates it with par. F-18 Motor Speed Low Limit [RPM] (par. F-16 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the How to Control the AF-600 FP section.

5.6.3 Nom Motor Speed [RPM]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciNmlSpeed

SNVT_rpm

1420 RPM

10 RPM

65,534 RPM

This variable configures the nominal motor speed in RPM and associates it with par. P-06 Base Speed.

NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 10 RPM is entered, nciNmlSpeed will be set to 10 RPM.

5.6.4 Nominal Motor Frequency [Hz]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciNmlFreq

SNVT_freq_hz

50 Hz

20 Hz

100 Hz

This variable configures the nominal motor frequency and associates it with par. F-04 Base Frequency.

NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 20 Hz is entered, nciNmlFreq will be set to 20 Hz.