Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 26

Advertising
background image

Alarm Flag

Variable
name:

SNVT
type:

State:

Value:

Command:

nvoAlarm

SNVT_switch

0 (False)

0

No alarm(s) present

1

(True)

100

Alarm(s)

present

This variable indicates whether any alarm is present.

Warning Flag

Variable
name:

SNVT
type:

State:

Value:

Command:

nvoWarning

SNVT_switch

0 (False)

0

No warning(s) present

1

(True)

100

Warning(s)

present

This variable indicates whether any warning is present.

Alarm Word

Variable
name:

SNVT
type:

State:

nvoAlarmword

SNVT_state_64

Boolean 1 bit x 64

This variable contains the complete alarm word.
For more detailed information on the Alarm Word, please refer to the Troubleshooting section of this manual.

NB!
Please note that in the representation of the Alarm Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.

Warning Word

Variable
name:

SNVT
type:

State:

nvoWarningword

SNVT_state_64

Boolean 1 bit x 64

This variable contains the complete warning word.
For more detailed information on the Warning Word, please refer to the Troubleshooting section of this manual.

NB!
Please note that in the representation of the Warning Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.