Par.o-50 coasting select t, Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 50

Advertising
background image

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid control word following a time-out. This parameter is active only
when par.O-04 Control Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in par.O-04 Control Word Timeout Function and displays a warning, until
par.O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.

[1] *

Resume set-up

Resumes the set-up active prior to the time-out.

O-06 Reset Control Word Timeout

Option:

Function:

This parameter is active only when the choice Hold set-up [0] has been selected in par.O-05 End-of-
Timeout Function
.

[0] *

Do not reset

Retains the set-up specified in par.O-04 Control Word Timeout Function, [Select setup 1-4] following a
control time-out.

[1]

Do reset

Returns the drive to the original set-up following a control word time-out. When the value is set to Do
reset
[1], the drive performs the reset and then immediately reverts to the Do not reset [0] setting.

O-07 Diagnosis Trigger

Option:

Function:

This parameter has no function for LonWorks.

[0] *

Disable

[1]

Trigger on alarms

[2]

Trigger alarm/warn.

O-10 Control Word Profile

Option:

Function:

Select the interpretation of the control and status words corresponding to the installed network. Only the
selections valid for the network installed in slot A will be visible in the keypad display.

[0] *

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

[7]

CANopen DSP 402

O-50 Coasting Select

Option:

Function:

Select control of the coasting function via the terminals (digital input) and/or via the network.

[0]

Digit Input

Activates Start command via a digital input.

[1]

Bus

Activates Start command via the serial communication port or network option module.

[2]

Logic AND

Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.

[3] *

Logic OR

Activates Start command via the network/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.

AF-600 FP LonWorks

49

8