Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 18

Advertising
background image

Output variables

Variable function

Variable name

SNVT type

Profile

AF-600 FP Par.

Status word

nvoStatusword

SNVT_state

Drive VSD

DR-03

Drive output [%]

nvoOutputPcnt

SNVT_lev_percent

Drive VSD

DR-05

Drive output [Hz]

nvoOutputHz

SNVT_freq_hz

Drive VSD

DR-13

kWh counter

nvoDrvEnrg

SNVT_elec_kwh_l

Drive VSD

ID-02

DC Link Voltage

nvoDCVoltage

SNVT_volt

Drive VSD

DR-30

Motor thermal

nvoTempMtr

SNVT_lev_cont

Drive VSD

DR-18

Inverter Thermal

nvoTempInvrtr

SNVT_lev_cont

Drive VSD

DR-35

Closed loop feedback

nvoFeedback

SNVT_count_inc_f

Drive VSD

DR-52

Fanbelt broken

nvoBrokenBelt

SNVT_switch

Drive VSD

DR-93

Alarm flag

nvoAlarm

SNVT_switch

Drive VSD

DR-90

Warning flag

nvoWarning

SNVT_switch

Drive VSD

DR-03

Alarm word

nvoAlarmword

SNVT_state_64

Drive VSD

DR-90 + DR-91

Warning word

nvoWarningword

SNVT_state_64

Drive VSD

DR-92 + DR-93

Extended statusword

nvoExtendedStatusword

SNVT_state_64

Drive VSD

DR-94 + DR-95

Digital inputs

nvoDigitInput

SNVT_state_64

Drive VSD

DR-60

Analog Input (53)

nvoAnIn1

SNVT_volt/SNVT_amp_mil/SNVT_lev_percent

Drive VSD

DR-62

Analog Input (54)

nvoAnIn2

SNVT_volt/SNVT_amp_mil/SNVT_lev_percent

Drive VSD

DR-64

Analog Input (X30/11)

nvo101AnIn1

SNVT_volt/SNVT_lev_percent

Drive VSD

DR-75

Analog Input (X30/12)

nvo101AnIn2

SNVT_volt/SNVT_lev_percent

Drive VSD

DR-76

Analog Input (X42/1)

nvo109AnIn1

SNVT_volt/SNVT_temp_p/SNVT_lev_percent

Drive VSD

LG-30

Analog Input (X42/3)

nvo109AnIn2

SNVT_volt/SNVT_temp_p/SNVT_lev_percent

Drive VSD

LG-31

Analog Input (X42/5)

nvo109AnIn3

SNVT_volt/SNVT_temp_p/SNVT_lev_percent

Drive VSD

LG-32

Parameter access cmd.

nvoParamResponse

UNVT_param_response

Drive VSD

-

AF-600 FP LonWorks

17

5

Advertising