Af-600 fp lonworks, 8 led behaviour – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 13

Advertising
background image

4.1.8 LED Behaviour

MS: Service LED (red)

Situation

LED

Description

Configured state (Nornal operation)

½ sec. ON, then continously OFF

The node is configures and running normally

Non configures state

Flashing ½ Hz

Node is not configures but has an application.
Proceed with loading node.

Applicationlessstate

1 sec. ON, 2 sec. OFF, then continuosly ON Node has no application, the LonWorks option

needs replacing or reprogramming

Watchdog resets

Short flash about each 3 sec.

Indicates problem with application. The Lon-
Works option needs replacing

Faulty hardware

Steady ON or OFF

The LonWorks option needs replacing

NS: Status LED (green)

Situation

LED

Description

Node configured

Steady ON

The node is configured and running
normally

Wink service

Flashing ½ Hz for 20 sec.

Wink service activated in order to
identify node.

AF-600 FP LonWorks