O-51 Quick Stop Select

Select control of the Quick Stop function via the terminals (digital input) and/or via the network.

Option:

Function:

[0]

Digital Input

[1]

Bus

[2]

Logic AND

[3] *

Logic OR

NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.

O-52 DC Brake Select

Option:

Function:

Select control of the DC brake via the terminals (digital input) and/or via the network.

[0]

Digit Input

Activates Start command via a digital input.

[1]

Bus

Activates Start command via the serial communication port or network option module.

[2]

Logic AND

Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.

[3] *

Logic OR

Activates Start command via the network/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.

O-53 Start Select

Option:

Function:

Select control of the drive start function via the terminals (digital input) and/or via the network.

[0]

Digit Input

Activates Start command via a digital input.

[1]

Bus

Activates Start command via the serial communication port or network option module.

[2]

Logic AND

Activates Start command via the network/serial communication port, AND additionally via one of the
digital inputs.

[3] *

Logic OR

Activates Start command via the network/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.

O-54 Reversing Select

Option:

Function:

Select control of the drive reverse function via the terminals (digital input) and/or via the fieldbus.

[0] *

Digit Input

Activates Reverse command via a digital input.

[1]

Bus

Activates Reverse command via the serial communication port or fieldbus option.

[2]

Logic AND

Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.

[3]

Logic OR

Activates Reverse command via the fieldbus/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par.O-01 Control Site is set to [0] Digital and control word.

AF-600 FP LonWorks