Analog Input (X42/1)

Variable
name:

SNVT
type:

Value:

nvo109AnIn1

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_temp_p

-273.15 °C

327.66 °C

0.01 °C

SNVT_lev_percent

0 %

100 %

0,1 %

Analog Input (X42/3)

Variable
name:

SNVT
type:

Value:

nvo109AnIn2

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_temp_p

-273.15 °C

327.66 °C

0.01 °C

SNVT_lev_percent

0 %

100 %

0,1 %

Analog Input (X42/5)

Variable
name:

SNVT
type:

Value:

nvo109AnIn3

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_temp_p

-273.15 °C

327.66 °C

0.01 °C

SNVT_lev_percent

0 %

100 %

0,1 %

These variables contain the value allocated to the analog input terminal X42/1-5 of the (OPCAIO) Analog I/O Option Module. The variable type is changeable with
the commissioning tool.

NB!
This variable is available only if the Analog I/O Option Module (OPCAIO) has been installed in the frequency converter.

Parameter Access Response

Variable name:

SNVT type:

nvoParamResponse

UNVT_param_response

This output variable is used for the frequency converter access.
A special UNVT has been defined for this variable.
For more information on parameter access, please refer to the How to Access AF-600 FP Parameters section.