Bit 10, Data not valid / Data valid:
This bit tells the frequency converter whether the control word is to be used or ignored. Bit 10 set to [0] causes the control word to be ignored.
Bit 10 set to [1] causes the control word to be used.
The control word is always contained in the telegram, regardless of which type of telegram is used, so this function is useful for ‘turning off’ the control word when
not required for updating or for reading parameters.

Bit 11, Relay 01:
Bit 11 set to [0] means that Relay is not activated.
Bit 11 set to [1] activates Relay 01, provided Control word bit 11 [36] has been chosen in par. E-24 Function Relay.

Bit 12, Relay 04:
Bit 12 set to [0] means that Relay 04 has not been activated.
Bit 12 set to [1] activates Relay 04, provided Control word bit 12 [37] has been chosen in par. E-24 Function Relay.

Bit 13 and 14, Selection of set-up:
Bits 13 and 14 are used to select one of four menu set-ups according to the following table:

Set-up

Bit 14

Bit 13

1

0

0

2

0

1

3

1

0

4

1

1

The function is only possible when Multi-Set-up [9] is selected in par. K-10 Active Set-up.

NB!
In par.O-55 Set-up Select, a selection is made to define how Bit 13/14 gates with the corresponding function on the digital inputs.

Bit 15, Reverse:
Bit 15 set to [0] causes no reversing.
Bit 15 set to [1] causes reversing.
Note: par. H-08 Reverse Lock determines if reversing is possible.