7 node object, Af-600 fp lonworks, 1 node object – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 35: 2 object request, 3 object response, 4 max. send time (heartbeat)

Advertising
background image

5.7 Node Object

5.7.1 Node Object

These variables are used for controlling all functional blocks via the commis-
sioning tool.

5.7.2 Object Request

Variable name:

SNVT type:

Supported functions:

Description:

nviRequest

SNVT_obj_request

RQ_Normal

Returns the specified functional block to normal operation.

RQ_Update_Status

Requests the status of the specified functional block.

RQ_Report_Mask

Requests a status mask reporting the status bits that are supported by

the specified functional block.

RQ_Disabled

Requests the specified functional block to change to the disabled state.
In the disabled state, output network variables belonging to the func-

tional block are not propagated within the network.

RQ_Enable

Requests the specified functional block to change to the enabled state.

In the enabled state, output network variables belonging to the func-

tional block are propagated within the network as defined by the

functional block.

5.7.3 Object Response

Variable name:

SNVT type:

Description:

nvoStatus

SNVT_object_status

This output network variable reports the status for any functional block on a device. It is also used to report the status

of the entire device and all functional blocks on the device.

5.7.4 Max. Send Time (Heartbeat)

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciMaxStsSendT

SNVT_elapsed_tm

00:0:0:0

00:0:0:0

017:59:59:999

This variable configures a timer to send the nvoStatus object but only if bound to an input variable.
Maximum is '0 17:59:59:999' (0 days, 17 hours, 59 minutes, 59 seconds and 999 milliseconds).
Setting the timer to '0 0:0:0:0' disables it.

Network timer functions monitor node presence and control behavour in the event of network problems occurring.

AF-600 FP LonWorks

34