Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual
Page 23
These variables contain the value allocated to the analog output terminal X42/7-11 of the Analog I/O option. The variable type is changeable with the commissioning
tool.
NB!
This variable is available only if the Analog I/O Option Module (OPCAIO) has been installed in the frequency converter.
Setting of RTC
Variable
name:
SNVT
type:
Field:
nviTimeStamp
SNVT_time_stamp
Year
Month
Day
Hour
Minute
Second
2000 -3000
0 - 12
0 - 31
0 - 23
0 - 59
0 - 59
Use this input to set the built-in Real Time Clock.
Parameter Access Command
Variable
name:
SNVT
type:
Value:
nviParamRequest
SNVT_param_request
These input variables are used for for frequency converter parameter access.
For more information on parameter access, please refer to How to Access AF-600 FP Parameters section.
AF-600 FP LonWorks
22