2 ge drive control profile, Af-600 fp lonworks, 1 drive control profile – GE Industrial Solutions AF-600 FP Lonworks User Manual
Page 39
NB!
Please refer to the Troubleshooting section to see an example of reference scaling.
All references provided to the frequency converter are added to the total reference value.
If a reference is to be controlled by the LonWorks bus only, please ensure that all other reference inputs are zero.
This means that digital and analog input terminals should not be used for reference signals.
The default setting (0%) should be maintained for preset references in par. C-05 Multi-step Frequency 1 - 8
6.2 GE Drive Control Profile
6.2.1 Drive Control Profile
Control Word According to Drive Profile
(Par. O-10 set to Drive Profile)
Bit
Bit value=0
Bit value=1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output freq.
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection lsb
14
Parameter set-up
Selection msb
15
No function
Reverse
AF-600 FP LonWorks
38
6