2 ge drive control profile, Af-600 fp lonworks, 1 drive control profile – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 39

Advertising
background image

NB!
Please refer to the Troubleshooting section to see an example of reference scaling.
All references provided to the frequency converter are added to the total reference value.
If a reference is to be controlled by the LonWorks bus only, please ensure that all other reference inputs are zero.
This means that digital and analog input terminals should not be used for reference signals.
The default setting (0%) should be maintained for preset references in par. C-05 Multi-step Frequency 1 - 8

6.2 GE Drive Control Profile

6.2.1 Drive Control Profile

Control Word According to Drive Profile
(Par. O-10 set to Drive Profile
)

Bit

Bit value=0

Bit value=1

00

Reference value

External selection lsb

01

Reference value

External selection msb

02

DC brake

Ramp

03

Coasting

No coasting

04

Quick stop

Ramp

05

Hold output freq.

Use ramp

06

Ramp stop

Start

07

No function

Reset

08

No function

Jog

09

Ramp 1

Ramp 2

10

Data invalid

Data valid

11

No function

Relay 01 active

12

No function

Relay 04 active

13

Parameter set-up

Selection lsb

14

Parameter set-up

Selection msb

15

No function

Reverse

AF-600 FP LonWorks

38

6