Af-600 fp lonworks, 3 drive vsd profile – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 17

Advertising
background image

5.1.3 Drive VSD Profile

The drive VSD Profile describes all GE drive specific network variables.

Input variables

Variable Function

Variable Name

SNVT type

Profile

AF-600 FP Par.

Start/Stop

nviStartStop

SNVT_switch

Drive VSD

CTW/reference

Control word

nviControlword

SNVT_state

Drive VSD

CTW

Reset fault

nviResetFaut

SNVT_switch

Drive VSD

CTW

Reference [%]

nviRefPcnt

SNVT_lev_percent

Drive VSD

Reference

Reference [Hz]

nviRefHz

SNVT_freq_hz

Drive VSD

Reference

CL Setpoint 1

nviSetpoint1

SNVT_lev_percent

Drive VSD

CL-21

CL Setpoint 2

nviSetpoint2

SNVT_lev_percent

Drive VSD

CL-22

CL Setpoint 3

nviSetpoint3

SNVT_lev_percent

Drive VSD

CL-23

Bus feedback 1

nviFeedback1

SNVT_lev_percent

Drive VSD

O-94

Bus feedback 2

nviFeedback2

SNVT_lev_percent

Drive VSD

O-95

Bus feedback 3

nviFeedback3

SNVT_lev_percent

Drive VSD

O-96

Digital/relay outputs

nviDigiOutput

SNVT_state_64

Drive VSD

E-90

Analog output (42)

nviAnOut1

SNVT_lev_percent

Drive VSD

AN-53

Analog output (X30/8)

nvi101AnOut1

SNVT_lev_percent

Drive VSD

AN-63

Analog output (X42/7)

nvi109AnOut1

SNVT_lev_percent

Drive VSD

AO-43

Analog output (X42/9)

nvi109AnOut2

SNVT_lev_percent

Drive VSD

AO-53

Analog output (X42/11)

nvi109AnOut3

SNVT_lev_percent

Drive VSD

AO-63

Setting of RTC

nviTimeStamp

SNVT_time_stamp

Drive VSD

K-70

Parameter access command nviParamRequest

UNVT_param_request

Drive VSD

-

AF-600 FP LonWorks

16

5