O-03 Control Word Timeout Time
Range:
Function:
60.0 s*
[1.0 - 18000.0 s]
Enter the maximum time expected to pass between the reception of two consecutive messages. If this
time is exceeded, it indicates that the serial communication has stopped. The function selected in
par.O-04 Control Word Timeout Function Control Time-out Function will then be carried out.
In LonWorks the following variables will trigger the Control Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
O-04 Control Word Timeout Function
Option:
Function:
Select the time-out function. The time-out function is activated when the control word fails to be updated
within the time period specified in par.O-03 Control Word Timeout Time. Choice [20] only appears after
setting the Metasys N2 protocol.
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.O-03 Control Word Timeout
Time:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz