Af-600 fp lonworks – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 49

Advertising
background image

[4]

Option B

[5]

Option C0

[6]

Option C1

[30]

External Can

NB!
This parameter cannot be adjusted while the motor is running.

O-03 Control Word Timeout Time

Range:

Function:

60.0 s*

[1.0 - 18000.0 s]

Enter the maximum time expected to pass between the reception of two consecutive messages. If this
time is exceeded, it indicates that the serial communication has stopped. The function selected in
par.O-04 Control Word Timeout Function Control Time-out Function will then be carried out.

In LonWorks the following variables will trigger the Control Word Time parameter:

nviStartStop

nviReset Fault

nviControlWord

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

O-04 Control Word Timeout Function

Option:

Function:

Select the time-out function. The time-out function is activated when the control word fails to be updated
within the time period specified in par.O-03 Control Word Timeout Time. Choice [20] only appears after
setting the Metasys N2 protocol.

[0] *

Off

[1]

Freeze output

[2]

Stop

[3]

Jogging

[4]

Max. speed

[5]

Stop and trip

[7]

Select setup 1

[8]

Select setup 2

[9]

Select setup 3

[10]

Select setup 4

[20]

N2 Override Release

In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.O-03 Control Word Timeout
Time
:

nviStartStop

nviReset Fault

nviControlWord

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

AF-600 FP LonWorks