Analog Input (54)

Variable
name:

SNVT
type:

Value:

nvoAnIn1

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_amp_mil

0 mA

20 mA

0.1 mA

SNVT_lev_percent

0 %

100 %

0,1 %

This variable contains the value allocated to the analog input terminal 54.
This terminal can either be configured as a voltage input (0-10 V) or as a current input (0-20 mA), depending on the setting of switch S 202. The variable type is
changeable with the commissioning tool in order to match the appropriate unit.

If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par. AN-21 Terminal 54 High Voltage or par. AN-23 Terminal 54 High
Current

Analog Input (X30/11)

Variable
name:

SNVT
type:

Value:

nvo101AnIn1

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_lev_percent

0 %

100 %

0,1 %

This variable contains the value allocated to the analog input terminal X30/11 of the (OPCGPIO) General Purpose I/O Option Module.

If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. AN-31 Terminal X30/11 High Voltage.

NB!
This variable is available only if the General Purpose I/O Option Module (OPCGPIO) has been installed in the frequency converter.

Analog Input (X30/12)

Variable
name:

SNVT
type:

Value:

nvo101AnIn2

Changeable

Min.

Max.

Resolution:

SNVT_volt

0 V

10 V

0.1 V

SNVT_lev_percent

0 %

100 %

0,1 %

This variable contains the value allocated to the analog input terminal X30/12 of the OPCGPIO General Purpose I/O Option Module.

If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. AN-41 Terminal X30/12 High Voltage.

NB!
This variable is available only if the General Purpose I/O Option Module (OPCGPIO) has been installed in the frequency converter.