Af-600 fp lonworks, 2 input variables (nvi), 3 configuration properties (nci) – GE Industrial Solutions AF-600 FP Lonworks User Manual

Page 62

Advertising
background image

9.4.2 Input Variables (nvi)

Variable Function

Variable Name

SNVT type

Profile

AF-600 FP Par.

Start/Stop

nviStartStop

SNVT_switch

Drive VSD

CTW/reference

Control word

nviControlword

SNVT_state

Drive VSD

CTW

Reset fault

nviResetFaut

SNVT_switch

Drive VSD

CTW

Reference [%]

nviRefPcnt

SNVT_lev_percent

Drive VSD

Reference

Reference [Hz]

nviRefHz

SNVT_freq_hz

Drive VSD

Reference

CL Setpoint 1

nviSetpoint1

SNVT_lev_percent

Drive VSD

CL-21

CL Setpoint 2

nviSetpoint2

SNVT_lev_percent

Drive VSD

CL-22

CL Setpoint 3

nviSetpoint3

SNVT_lev_percent

Drive VSD

CL-23

Bus feedback 1

nviFeedback1

SNVT_lev_percent

Drive VSD

O-94

Bus feedback 2

nviFeedback2

SNVT_lev_percent

Drive VSD

O-95

Bus feedback 3

nviFeedback3

SNVT_lev_percent

Drive VSD

O-96

Digital/relay outputs

nviDigiOutput

SNVT_state_64

Drive VSD

E-90

Analog output (42)

nviAnOut1

SNVT_lev_percent

Drive VSD

AN-53

Analog output (X30/8)

nvi101AnOut1

SNVT_lev_percent

Drive VSD

AN-63

Analog output (X42/7)

nvi109AnOut1

SNVT_lev_percent

Drive VSD

AO-43

Analog output (X42/9)

nvi109AnOut2

SNVT_lev_percent

Drive VSD

AO-53

Analog output (X42/11)

nvi109AnOut3

SNVT_lev_percent

Drive VSD

AO-63

Setting of RTC

nviTimeStamp

SNVT_time_stamp

Drive VSD

K-70

Parameter access command

nviParamRequest

UNVT_param_request

Drive VSD

-

Drive speed setpoint

nviDrvSpeedStpt

SNVT_switch

VSD 6010

CTW / Reference

Standard Node Object

nviRequest

SNVT_obj_request

Node obj.

-

9.4.3 Configuration Properties (nci)

Variable function

Variable name

SNVT type

Profile

AF-600 FP

Par.

Max. motor speed [%]

nciMaxSpeed

SNVT_lev_percent

VSD 6010

F-17

Min. motor speed [%]

nciMinSpeed

SNVT_lev_percent

VSD 6010

F-18

Nom. motor speed [RPM]

nciNmlSpeed

SNVT_rpm

VSD 6010

P-06

Nom. motor frequency [Hz]

nciNmlFreq

SNVT_freq_hz

VSD 6010

F-04

Min. ramp-up time [s]

nciRampUpTime

SNVT_time_sec

VSD 6010

F-07

Min. ramp-down time [s]

nciRampDownTime

SNVT_time_sec

VSD 6010

F-08

Heartbeat time [s]

nciSndHrtBt

SNVT_time_sec

VSD 6010

-

Max Send Time (Heartbeat)

nciMaxStsSendT

SNVT_elapsed_tm

Node obj.

-

Min Send Time (Inhibit timer)

nciMinSendT

SNVT_elapsed_tm

Virtual obj.

-

AF-600 FP LonWorks

61

9

Advertising