5.3.4 Configuration Properties (nci)

Variable function

Variable name

SNVT type

Profile

AF-600 FP pa-

rameter

Max. motor speed [%]

nciMaxSpeed

SNVT_lev_percent

VSD 6010

F-17

Min. motor speed [%]

nciMinSpeed

SNVT_lev_percent

VSD 6010

F-18

Nom. motor speed [RPM]

nciNmlSpeed

SNVT_rpm

VSD 6010

P-06

Nom. motor frequency [Hz]

nciNmlFreq

SNVT_freq_hz

VSD 6010

F-04

Min. ramp-up time [s]

nciRampUpTime

SNVT_time_sec

VSD 6010

F-07

Min. ramp-down time [s]

nciRampDownTime

SNVT_time_sec

VSD 6010

F-08

Heartbeat time [s]

nciSndHrtBt

SNVT_time_sec

VSD 6010

-

A range of network configuration variables (SCPT's) is available for configuration of the frequency converter parameters. These parameters require setting only
once, usually following installation.

NB!
Please note that the settings written to configuration properties (nci's) will be stored in the non-volatile memory. Continuous writing to configuration properties
may damage the non-volatile memory.

5.4 Network Variable Description - VSD Profile - input

5.4.1 Frequency Converter Speed Setpoint

Variable name:

SNVT type:

State:

Value:

Command:

nviDrvSpeedStpt

SNVT_switch

0 (False)

Any

Stop

1 (True)

0

Running 0 %

1 (True)

1-200

Running 0.5 to 100 %

1 (True)

201-255

Running 100 %

0xFF (default)

Any

AUTO (invalid, no action)

This input variable provides start / stop control and a speed reference.

AF-600 FP LonWorks

30