5.2.2 Network Variable Description - Drive VSD Profile - Output

Status Word

Variable name:

SNVT type:

State:

nvoStatusWord

SNVT_state

Boolean 1 bit x 16

This variable is a 16-bit word providing status information on the frequency converter. For more information on the status word, please refer to the GE Drive
Control Profile
section.

NB!
Please note that in the representation of the Status Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.

Drive Output [%]

Variable
name:

SNVT
type:

Value:

nvoOutputPcnt

SNVT_lev_percent

Min.

Max.

Resolution:

-163.840

%

+163.840

%

0.005

%

In open loop operation, this variable contains the frequency converter output frequency in percentage, within the reference range.
In closed loop operation, this variable contains the frequency converter feedback signal, within the reference range.

Drive Output [Hz]

Variable
name:

SNVT
type:

Value:

nvoOutputHz

SNVT_freq_hz

Min.

Max.

Resolution:

0 Hz

6,500 Hz

1 Hz

This variable displays the actual output of the frequency converter motor frequency in Hz.

kWh Counter [kWh]

Variable
name:

SNVT
type:

Value:

nvoDrvEnrg

SNVT_elec_kwh_l

Min.

Max.

Resolution:

0 kWh

219,748,364.8 kWh

1 kWh

This variable contains the power consumption of the motor in kWh measured as a mean value over a one hour period.