5.6.5 Min Ramp-up Time [s]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciRampUpTime

SNVT_time_sec

10 s

1 s

3,600 s

This variable configures the ramp-up time and associates it with par. F-07 Accel Time 1.

5.6.6 Min Ramp-down Time [s]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciRampDownTime

SNVT_time_sec

10 s

1 s

3,600 s

This variable configures the ramp-down time and compares it with par. F-08 Decel Time 1.

5.6.7 Heartbeat Time [s]

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciSndHrtBt

SNVT_time_sec

0 s

0 s

6,553.4 s

This variable configures a heartbeat timer to send the following variables:

nvoDrvCurnt

nvoDrvSpeed

nvoDrvVolt

nvoDrvPwr

Setting the timer to 0.0 disables the timer.

Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling management systems to prove that the node is present
on the network and working correctly. Only bound variables will be transmitted.

AF-600 FP LonWorks

33