In the [Field List:] under the section [par_number], enter the parameter number (in this example F-07). If an indexed (array) parameter is accessed, the [subindex]
field must be filled-in.

The response may look like this:

Value [0] (1st byte) = 232

Value [1] (2nd byte) = 3

-meaning that the readout value of parameter F-07 is: 232+(3x256) = 1000
Conversion index of par. F-07 is: -2(0.01)

Acdel time 1 = 1000x0.01 = 10 seconds

AF-600 FP LonWorks