6.2.3 Status Word According to Drive Profile (STW)

Parameter O-10 set to [Drive profile]

Bit

Bit value=0

Bit value=1

00

Control not ready

Control ready

01

Drive not ready

Drive ready

02

Coasting

Enable

03

No error

Trip

04

No error

Error (no trip)

05

Reserved

-

06

No error

Trip lock

07

No warning

Warning

08

Speed # reference

Speed = reference

09

Local operation

Bus control

10

Out of frequency

limit

Frequency

limit ok

11

No operation

In operation

12

Brake ok

Brake warning or failure

13

Voltage ok

Voltage exceeded

14

Torque ok

Torque exceeded

15

Timer ok

Timer exceeded

6.2.4 Explanation of the Status Bits

Bit 00, Control not ready / ready:
Bit 00 set to [0] means that the frequency converter has tripped.
Bit 00 set to [1] means that the frequency converter controls are ready, but that the power component is not necessarily receiving any power supply (in the event
of external 24 V supply to controls).

Bit 01, Drive ready:
Bit 01 set to [1] means that the frequency converter is ready for operation, but it is receiving an active coasting command via the digital inputs or via serial
communication.

Bit 02, Coasting stop:
Bit 02 set to [0] means that the frequency converter has released the motor.
Bit 02 set to [1] means that the frequency converter can start the motor when a start command is given.

Bit 03, No error / trip:
Bit 03 set to [0] means that the frequency converter is not in fault mode.
Bit 03set to [1] means that the frequency converter is tripped and that a reset signal is required to re-establish operation.

Bit 04, No error / error (no trip):
Bit 04 set to [0] means that the frequency converter is not in fault mode.
Bit 04 set to [1] means that there is a frequency converter error but no trip.

Bit 05, Not used:
Bit 05 is not used in the status word.

Bit 06, No error / trip lock:
Bit 06 set to [0] means that the frequency converter is not in fault mode.
Bit 06 set to [1] means that the frequency converter is tripped and locked.

Bit 07, No warning / warning:
Bit 07 set to [0] means that there are no warnings.
Bit 07 set to [1] means that a warning has occurred.

Bit 08, Speed # reference / speed = reference:
Bit 08 set to [0] means that the motor is running, but that the present speed is different from the preset speed reference. For example, this might occur while the
speed is being ramped up/down during start/stop.
Bit 08 set to [1] means that the present motor speed matches the preset speed reference.