5.8 Network Timer Functions

5.8.1 Control Word Time-out Function

par.O-03 Control Word Timeout Time and par.O-04 Control Word Timeout Function provide a means for the frequency converter to control communication to a
controller node.
If a valid control word has not been received within the time specified in par. O-03, the action specified in par. O-04 will be performed. The default action is OFF
(no action).
The range of par. O-03 is: 0.1 to 18,000 seconds (or 5 hours).

An update of the control word is triggered by the following SNVT's:

nviStartStop

nviResetFault

nviControlword

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

nviFeedback 1,2,3

nviSetPoint 1,2,3

5.8.2 Min. Send Time (Inhibit Timer)

Variable
name:

SNVT
type:

Default value:

Min value:

Max value:

nciMinSendT

SNVT_elapsed_tm

00:0:0:500

0 0:0:0:100

0 0:01:05:535

Variable used for limiting bus traffic by setting a minimum sending timer (inhibit timer).
Applies for all output variables.
Format: Days Hours:Minutes:Seconds:Milliseconds.

AF-600 FP LonWorks