Specifications, Timing specifications, Protection specifications – GE Industrial Solutions MX350 Instruction manual User Manual

Page 10: Specifications - 6

Advertising
background image

1–6

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

SPECIFICATIONS

CHAPTER 1: INTRODUCTION

Specifications

NOTE

NOTE:

Specifications are subject to change without notice.

Timing specifications

GENERAL TIMING ACCURACY

Accuracy:................................................................±500 ms

Protection specifications

OVERVOLTAGE

Pickup level:...........................................................1.05 to 1.10 × VT in steps of 0.01 (programmable)
Dropout: ..................................................................1.03 to 1.08 × VT in steps of 0.01 (programmable)
Time delay: ............................................................No programmable time delay

UNDERVOLTAGE

Pickup level:...........................................................0.75 to 0.99 × VT in steps of 0.01 (programmable)
Dropout: ..................................................................0.85 to 1.00 × VT in steps of 0.01 (programmable)
Time delay: ............................................................No programmable time delay

OVERFREQUENCY

Pickup level:...........................................................50.1 to 63.0 Hz in steps of 0.1 (programmable)
Dropout: ..................................................................50.0 to 62.9 Hz in steps of 0.1 (programmable)
Time delay: ............................................................No programmable time delay
Accuracy:................................................................±0.05 Hz

UNDERFREQUENCY

Pickup level:...........................................................45.0 to 59.9 Hz in steps of 0.1 (programmable)
Dropout: ..................................................................45.1 to 60.0 Hz in steps of 0.1 (programmable)
Time delay: ............................................................No programmable time delay
Accuracy:................................................................±0.05 Hz

POWER FACTOR

Pickup level:...........................................................0.99 lag to 0.99 lead in steps of 0.01 (programmable)
Dropout: ..................................................................pickup + hysteresis
Time delay: ............................................................0 to 65535 seconds in steps of 1
Accuracy:................................................................±0.05

VOLTAGE IMBALANCE

Pickup level:...........................................................0.05 to 0.20 in steps of 0.01 (programmable)
Dropout: ..................................................................0.03 to 0.18 in steps of 0.01 (programmable)
Time delay: ............................................................1 to 60 seconds in steps of 1

CURRENT IMBALANCE

Range:......................................................................4 to 40% in steps of 1
Pickup level:...........................................................0.04 to 0.40 in steps of 0.01 (programmable)
Time delay: ............................................................1 to 60 seconds in steps of 1 s
Timing accuracy: ................................................±500 ms
Elements:................................................................alarm
Accuracy:................................................................±2%