CHAPTER 2: INSTALLATION

ELECTRICAL INSTALLATION

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

2–7

Electrical installation

This section describes the electrical installation of the MX350 system. An overview of the
MX350 terminal connections is shown below.

Figure 8: MX350 terminal connection overview

The MX350 can contain up to ten modules. The first four modules (slots A through D) reside
in the base unit while all subsequent modules (slots E and J) reside in expansion units.
Each expansion unit can contain up to two modules. Slots A through G make up the basic
MX350. The next three modules (slots H through J) are optional I/O modules.

Table 2: Module slot position

The following figure shows a typical module arrangement for an expanded unit.

CAUTION

CAUTION:

Use gauge size appropriate for the voltage and current draw of the device.

The MX350 is not to be used in any way other than described in this manual.

Expansion module

Expansion module

to base unit with a

single connector

CT Input

Three-phase plus
ground/neutral
VT inputs

Optional TCP/IP
Ethernet

RS485 communications

Switched power supply
allows AC or DC control
voltage

889740A2.CDR

K Card

Expansion module

to base/expansion unit
with a single connector

L Card

L Card

Expansion module

Reserved

Reserved

Slot

Module types

A

Power supply module

B

CPU module with communications

C

IO_B module

D

IO_B module

E

IO_A module (optional)

F

IO_K module

G

IO_L module

H

IO_L module (optional)

I

IO_L module (optional)