Input/output modules, Phase current inputs (io_a module), Input/output modules - 10 – GE Industrial Solutions MX350 Instruction manual User Manual

Page 26

Advertising
background image

2–10

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

ELECTRICAL INSTALLATION

CHAPTER 2: INSTALLATION

Input/Output modules

Phase current inputs

(IO_A module)

Figure 11: Typical phase current input connections

The MX350 has three channels for phase current inputs, plus an additional channel input
for ground/neutral current, each with an isolating transformer. The phase CTs should be
chosen so the nominal current is not less than 50% of the rated phase CT primary. Ideally,
the phase CT primary should be chosen such that the nominal current is 100% of the
phase CT primary or slightly less, never more. This will ensure maximum accuracy for the
current measurements. The maximum phase CT primary current is 4000 A.
The MX350 measures up to 1.5 times the phase current nominal rating. CTs with 1 A or 5 A
secondaries must be used if the FLA is greater than 5 A. The chosen CTs must be capable
of driving the MX350 phase CT burden.

CAUTION

CAUTION:

Polarity of the phase CTs is critical for negative-sequence unbalance calculation,
power measurement, and residual ground current detection (if used).

A

C

B

Power flow

+

E1

E2

E4

E3

Phase current inputs

Automatic Transfer Control System

To switchgear

ground bus

889744A1.CDR

E5

E6

E7

CT1

CT2

CT3

Control power

L

N

E8

G/F

N