CHAPTER 2: INSTALLATION

ELECTRICAL INSTALLATION

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

2–13

Type IO_L module

connections

IO_L modules provide all user configurable I/O. Additionally, some of the I/O points on the
first L module in slot G are used for some factory configured I/O. The terminal
configuration is as follows:

NOTE

NOTE:

Terminals G7 and G8 are always used as DS and Q2, respectively. Depending on the type
of switch and the features ordered, Terminals G1 through G5 as well as G9 through G13
may not be available for customer configuration.

Figure 15: IO_L module - standard ATS

Terminal

Terminal

Terminal

Type

Function

G1

H1

J1

Output

Output 1

G2

H2

J2

Output

Output 2

G3

H3

J3

Output

Output 3

G4

H4

J4

Output

Output 4

G5

H5

J5

Output

Output 5

G6

H6

J6

Common

Common, Ouputs 1 to 5

G7

H7

J7

Input

Input 1

G8

H8

J8

Input

Input 2

G9

H9

J9

Input

Input 3

G10

H10

J10

Input

Input 4

G11

H11

J11

Input

Input 5

G12

H12

J12

Input

Input 6

G13

H13

J13

Input

Input 7

G14

H14

J14

Common

Common, Inputs 1 to 7

~1

~2

~4

~3

~5

~6

Auto Transfer Control

~8

~9

~11

~10

~12

~13

~7

~14

Inp
com

Inp 7

Inp 6

Inp 5

Inp 4

LOAD SHED FROM S2

TEST WITH LOAD

DISCONNECT SW

LOAD SHED FROM S2

SSR

COM

SSR3

SSR5

SSR4

SSR2

SSR1

NO

~1

~2

~4

~3

889742A1.CDR

~5

~6

Auto Transfer Control

~8

~9

~11

~10

~12

~13

~7

~14

Inp
com

In

SSR

SSR

NC

Inp 3

Inp 2

Inp 1

LOAD SHED

HARDWARE

FOR LOCAL

OPTION

TO BREAKER

24 V DC

0 VDC

0 VDC

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED

USER DEFINED