CHAPTER 3: INTERFACING WITH THE MX350 AT CONTROLLER

ENERVISTA™ MX350 SETUP SOFTWARE

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

3–29

Loading setpoints

from a file

CAUTION

CAUTION:

An error message will occur when attempting to download a setpoint file with a
revision number that does not match the relay firmware. If the firmware has been
upgraded since saving the setpoint file, see Upgrading Setpoint Files to a New Revision,
above, for instructions on changing the revision number of a setpoint file.

The following procedure illustrates how to load setpoints from a file. Before loading a
setpoints file, it must first be added to the environment as described in the section, Adding
Setpoints Files to the Environment
.
1.

Select the previously saved setpoints file from the File pane of the EnerVista™ MX350
Setup software main window.

2.

Select the Offline > Edit Settings File Properties menu item and verify that the
corresponding file is fully compatible with the hardware and firmware version of the
target relay. If the versions are not identical, see Upgrading Setpoint Files to a New
Revision
, above, for details on changing the setpoints file version.

3.

Right-click on the selected file and select the Write Settings File to Device item.

4.

Select the target relay from the list of devices shown and click Send. If there is an
incompatibility, an "Incompatible Device" error message will occur:

If there are no incompatibilities between the target device and the settings file, the data
will be transferred to the relay. An indication of the percentage completed will be shown at
the bottom of the main window.

Upgrading relay firmware

For firmware updates contact GE Zenith Service Group at 1-800-637-1738 x3.