CHAPTER 3: INTERFACING WITH THE MX350 AT CONTROLLER
POWER ANALYSIS
MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL
3–35
Viewing and saving of the Datalogger is performed as follows:
1.
With EnerVista™ MX350 Setup running and communications established, select the
Diagnostics > Datalog menu item to open the datalog setup window:
2.
If Continuous mode is enabled, click on Stop to stop the datalog
3.
Click on the Save to File button to save the datalog to the local PC. A new window will
appear requesting for file name and path.
4.
One file is saved as a COMTRADE file, with the extension ‘CFG’. The other file is a DAT
file, required by the COMTRADE file for proper display of data.
Setting
Parameter
Sample Rate
1 Second
Continuous Mode
Disabled
Data Log Trigger Position
25%
Data Log Trigger Source
None
Channel 1 Source
Phase A Current
Channel 2 Source
Phase B Current
Channel 3 Source
Phase C Current
Channel 4 Source
Disabled
Channel 5 Source
Disabled
Channel 6 Source
Disabled
Channel 7 Source
Disabled
Channel 8 Source
Disabled
Channel 9 Source
Disabled
Channel 10 Source
Disabled